BTK1008 Fire Alarm Control Panel is a digitize based unit designed for small to medium commercial, institutional and industrial occupancies.
The BTK1008 easy to install and manual
Indicating circuits which are each rated at 1.25 Amps. The panel also includes a 2.75 Amp Power Supply which powers the system and supplies a 4-wire resettable regulated smoke power supply of 24 VDC 100mA maximum. The BTK1008 utilizes a simple button configuration for programming initiating and indicating circuits as well as the enabling and disabling of system functions such as Signal Silence, Fire Drill and Auxiliary Disconnect. Supervisory. In addition the BTK1008 allows for Alarm Verification on the initiating circuits.
The cabinet is available in a red exterior color for the Thailandian market . Space is provided
for up to 7.2 AH batteries.
SPECIFICATIONS
No. of circuit10
Primary input powerAC 220V, 60Hz
Standby power 24VDC Standby Batteries
Charging capability 4-7.2AH Batteries
Circuit vontage24VDC
Rated current 4A
Usable environment -10˚C ~ 50˚C
Connection
No. of detector Different, fixed Temperature: Required No.
Smoking Type: Less than 25 for a circuit
Heat Type : Less than 15 for a circuit
Line resitance 10K
Circuit structure Relay Method
ColorRed
Dimensions (mm)300(W) x 420(H) x 100(D)